AT180G Direct Type Three Phase Din Rail Energy Meter

AT180G Direct Type Three Phase Din Rail Energy Meter series are designed to collect, analyze and measure power parameters. AT100G series single-phase din rail energy meter can support the measurement and analysis of various power parameters, such as voltage, current, four-quadrant power parameters, power factor, bi-directional active and reactive power etc.

Product Description

AT180G Direct Type Three Phase Din Rail Energy Meter series are designed to collect, analyze and measure power parameters. AT100G series single-phase din rail energy meter can support the measurement and analysis of various power parameters, such as voltage, current, four-quadrant power parameters, power factor, bi-directional active and reactive power etc. This series of products have RS485 communication interface, the highest baud rate support 38400bps, support Modbus, DLT645 and other communication protocols, can easily realize remote data reading. Meanwhile, it adopts LCD display, which can view and set various measurement parameters locally, and the product has password protection function to ensure the data security of the product.

Main Features

  • Multifunctional parameter measurement
  • Support bi-directional power metering
  • Support direct access type, CT variable ratio access
  • Support 1-channel pulse optocoupler output interface, output parameters configurable
  • Support RS485 communication function, support Modbus RTU protocol
  • Standard 4-mode digital width, TH35-7.5 type din rail mounting
  • Large LCD display, white backlight, backlight lighting time adjustable
  • LCD refresh time: 1 second, support manual page turning and automatic display rotation (can be set to switch)

 

Product Parameters

Measured parameters

 

Voltage
Current, current demand
Frequency
Power, maximum power demand and power factor
Forward and reverse active energy
Forward and reverse reactive power
Serial communication

 

RS485 serial port
Modbus-RTU protocol
Pulse Two pulse outputs
   Parameters Value
Applicable grid 3 phase 4 wires, 3 phase 3 wires
Working power Voltage range AC/DC85~265V
Power consumption <5VA
Accuracy Class Voltage, current ±0.5%
Power ±1%
Power Factor ±1%
Frequency ±0.2
Electricity ±1%
Frequency 45Hz~65Hz
Pulse constant 400imp/kWh
EMC electromagnetic compatibility test Electrostatic discharge immunity test GB/T 17626.2-2006:test level 4
RF electromagnetic field immunity test GB/T 17626.3-2006:test level 3
Fast transient pulse group test GB/T 17626.4-2008:test level 4
Surge (shock) immunity test GB/T 17626.5-2008:test level 4
RF field induction conducted harassment immunity test GB/T 17626.6-2008:test level 3

 