ATZ2000 Smart Power Analyzer

ATZ2000 is a multi-function power analyzer that can accurately measure and display various power parameters including voltage, current, power, frequency, active power, reactive power, forward power, reverse power, power factor, total harmonic distortion, sub-harmonics, maximum demand etc.

Product Description

ATZ2000 is a multi-function power analyzer that can accurately measure and display various power parameters including voltage, current, power, frequency, active power, reactive power, forward power, reverse power, power factor, total harmonic distortion, sub-harmonics, maximum demand etc. in single-phase two-wire, three-phase three-wire and three-phase four-wire grids. It is suitable for real-time power monitoring system as it is featured in multi-function, multi-purpose, high stability and long life, etc. The meter adopts external transformer access, suitable for various high and low-voltage grids, the maximum current can reach 9999A, the maximum voltage up to 500000V. With RS485 communication interface, support the highest communication rate 38400bps, can realize remote communication, is the ideal choice for power energy monitoring. Setting parameters can be achieved by touching the keys on the panel, easy to operate and with high security password protection.

Main Features

  • Cycle sampling not less than 128 points, support telematics, remote control, telemetry
  • Compatible with single-phase and three-phase full grid system type access
  • Sub-phase and total full power parameter measurement
  • Fractional harmonic measurement can reach up to 63 times
  • Support RS-485 and Ethernet port communication
  • Communication rate up to 38400bps
  • Five-touch key operation, friendly interface settings
  • High-resolution large screen, wide view area with black characters on gray background
  • Sub-phase and total power and current demand statistics
  • Demand calculation mode, update period, slip time can be set
  • Real-time display of the load ratio sector chart
  • Power factor histogram indication
  • Bidirectional metering, sub-phase active and reactive power metering
  • Unbalanced (NEUTRAL WIRE) current and voltage
  • Phase sequence judgment, phase angle display
  • Manual and automatic page flip, backlight delay can be set
  • 8 time periods setting, 4 tariff metering
  • 1A/5A transformer type access, variable ratio can be set
  • Intelligent setting of forward and reverse wiring of sub-phase transformer
  • DI input anti-shake time can be set according to actual needs
  • DO level and pulse output can be set according to actual needs
  • DO output delay time can be set according to actual needs
  • SOE equipment full event record
  • Removable battery for easy maintenance
  • Dn housing, installation size 92*92mm, extrusion type installation, no snap fastening needed
  • Plug and unplug connection

Product Parameters

Parameter Value
Applicable grid Three-phase four-wire, three-phase three-wire, single two-wire, three-phase three-wire PT
Working power Voltage range AC/DC85~265V
Power consumption

 

≤5W
Input Voltage Rated AC100V、220V、400V
Overload 1.2 times continuous, 2 times (10s)
Power consumption <0.4VA/Phase
Impedance ≥200kΩ
Current Primary current 1-9999A
Secondary input 1A or 5A
Short-time overcurrent 20 times the maximum current for 0.5 seconds
Power consumption <0.2VA/Phase
Impedance ≥0.1Ω
Frequency 45Hz~65Hz
Switching input Dry contact input, photoelectric isolation
Output Switching output Relay output; can set any alarming power, default remote control
Pulse output 1 channel electrical energy pulse
Accuracy index Voltage/current 0.5%
Frequency 0.2%
Power/power factor 1%
Active power Class0.5
Reactive power CLass2
Communication Bus type RS485
protocol Modbus RTU
Baud rate 2400/4800/9600/19200/38400bps
Address range 1-247
Bus load 64pcs
Communication distance 1000m
Parity EVEN/ODD/NONE(default)
Data bits 8
Stop bit 1
Ethernet por Modbus
Environment Operation temperature -25℃~55℃
Storage temperature -40℃~70℃
Operating humidity ≤90%RH, non-condensing, no corrosive air
Storage humidity ≤95%RH, non-condensing, no corrosive air
Altitude ≤2000m
Installation category CATIII
Withstanding voltage capacity AC withstanding voltage 4KV/1min Pulse withstanding voltage 6kV – 1.2µS waveform
IP Class IP51(Indoors)
Insulation class
Average trouble-free operation time ≥50000h
EMC electromagnetic compatibility test Electrostatic discharge immunity test GB/T 17626.2-2006:test level 4, test voltage 8kV
RF electromagnetic field immunity test GB/T 17626.3-2006:test level 3, test field strength of 10V / m
Fast transient pulse group test GB/T 17626.4-2008:test level 2, current voltage 1kV, other 500V
Surge (shock) immunity test GB/T 17626.5-2008:test level 4, test voltage 4kV
RF field induction conducted harassment immunity test GB/T 17626.6-2008:test level 3, test field strength of 10V / m
Voltage transients, short interruptions and voltage changes in the immunity test GB/T 17626.11-2008:current and voltage test error qualified
Oscillation wave immunity test GB/T 17626.12-1998:Class B ITE test, qualified
                               Conformity to Standards GBT22264.1-2008 Mounted digital display electrical measuring instrument Part 1: Definition and general requirements
GBT22264.7-2008 Mounted digital display electrical measuring instrument Part 7: Special requirements for multifunctional instruments
GBT22264.8-2009 Mounted digital display electrical measuring instrument Part 8:Recommended test methods

Product Chart