Energy Meter Series
AT181G-CT-4G Three-Phase Multifunction 4G Meter
Product Details
Application:
Photovoltaic Inverter System
Charging station infrastructure
Wind Power System
Power System Utilities / Future Communities
SCADA / Energy Management System
Functions
- Bidirectional active/reactive energy metering (forward/reverse)
- Real-time measurement of voltage, current, and power
- Demand measurement and peak demand recording
- Multi-tariff (4 rates, 8 time periods; optional)
- 4G communication
- Strong electromagnetic compatibility, suitable for industrial environments;
- Three-phase, four-wire full-parameter measurement (U, I, P, Q, S, PF, F);
- LCD display with local cyclic display or manual page turning;
- DIN-rail mounting to save space in switchgear;
- High insulation and withstand voltage, safety class CAT III
Parameters
|
Input voltage |
Rated Voltage |
230 VAC(phase voltage) / 400 VAC(line voltage) |
|
Direct access |
Measurement range: 176–276 VAC |
|
|
Measuring frequency range |
45~65 Hz |
|
|
Input current |
CT Primary side range |
1~9999 A |
|
CT Secondary Side Output |
Ratings: 1A/5A (default), 100mA/mV (optional) |
|
|
Pulse power output |
Output Mode |
Open-collector optocoupler pulses |
|
Pulse Frequency |
Can be set to: 0.001, 0.01, 0.1, or 1 kWh/kvarh per pulse |
|
|
Pulse Width |
Can be set to: 60, 100 (default), or 200 ms |
|
|
Pulse Output Type |
Can be set to: Forward/Reverse/Total Active or Reactive |
|
|
Output Level |
Class A, in accordance with IEC 62053-31 |
|
|
Input Voltage |
5–27 VDC |
|
|
Communication |
4G |
|
|
Accuracy |
Voltage/Current |
Class 0.5 |
|
Active power |
Class 0.5 |
|
|
Reactive power |
Class 2 |
|
|
Apparent power |
Class 1 |
|
|
Active power |
Class 0.5S |
|
|
Reactive power |
Class 2 |
|
|
Power factor |
Class 1 |
|
|
Frequency |
Class 0 |
|
Dimension

Wiring 3P4W