AT180 Three Phase Multi-function Digital Energy Meter

AT180 Three Phase Multi-function Digital Energy Meter is an ideal device for power monitoring. The instrument has the function of simultaneous measurement of current, voltage, frequency, active power, reactive power, apparent power, forward and reverse active power, forward and reverse reactive power, power factor, etc. in the power grid.

Product Description

AT180 Three Phase Multi-function Digital Energy Meter is an ideal device for power monitoring. The instrument has the function of simultaneous measurement of current, voltage, frequency, active power, reactive power, apparent power, forward and reverse active power, forward and reverse reactive power, power factor, etc. in the power grid. It is suitable for the distributed detection of transformers, generator sets, capacitor sets and motors, as well as the on-site monitoring of power grids and automation control systems.
This series of multifunctional energy meters can replace many traditional analog or digital measuring instruments (such as ammeter, voltmeter, power meter, power factor meter, frequency meter, etc.), which can greatly reduce the system cost, facilitate field wiring and improve the reliability of the system. The multifunctional energy meter is equipped with a serial port, allowing connection to an open computer network; the application of Modbus communication protocol makes it easy for the computer to program settings or read data.

Main Features

  • Three-phase power parameter calculation
  • Modular design, flexible configuration of each function
  • Adjustable voltage and current ratio
  • Parameter setting locked with password, permanent power failure storage
  • Support RS-485 communication, MODBUS-RTU protocol
  • Adopt AC-DC dual-use power supply, high and low voltage isolation
  • Digital tube high brightness display
  • Simple and convenient installation and wiring

 

Product Parameters

Measurement and metering
Voltage Phase voltage, line voltage
Current Three-phase current
Active power Split-phase and total active power
Reactive power Split-phase and total reactive power
Apparent power Split-phase and total apparent power
Power Factor Phase-to-phase and total power factor
Frequency 45-60Hz
Power measurement
active power forward/reverse active power
Reactive power Positive/reverse reactive power
Communication function

 

Communication protocol MODBUS-RTU
Communication mode RS485
Parameters Value
Applicable grid 3 phase 4 wires, 3 phase 3 wires
Working power Voltage range AC/DC85~265V;DC18V~72V(Optional)
Power consumption <5VA
Accuracy Class Active Power Class 1, others Class 0.5
Input Voltage Rated AC 100V、220V、400V
Power consumption <0.4VA/Phase
Impedance ≥200kΩ
Current Rated AC 5A(0.02A-6A)
Power consumption <0.2VA/Phase
Impedance ≥0.1Ω
Frequency 45Hz~65Hz
Switching input Dry contact input, photoelectric isolation
Output Switching output Relay output;

can set any alarming power, default remote control

Analog output 0~20mA/0~5V(Can be set)
Digital communication interface RS485/Modbus-RTU
Pulse output 1~2 channels electrical energy pulse,Four-quadrant power metering
Environment

 

Temperature Operation temperature: -20℃~55℃, Storage: -25℃~70℃
Humidity ≤90%RH, non-condensing, no corrosive air
Altitude ≤2500m
EMC electromagnetic compatibility test Electrostatic discharge immunity test GB/T 17626.2-2006:test level 4, test voltage 8kV
RF electromagnetic field immunity test GB/T 17626.3-2006:test level 3, test field strength of 10V / m
Fast transient pulse group test GB/T 17626.4-2008:test level 2, current voltage 1kV, other 500V
Surge (shock) immunity test GB/T 17626.5-2008: test level 4, test voltage 4kV
RF field induction conducted harassment immunity test GB/T 17626.6-2008: test level 3, test field strength of 10V / m
Voltage transients, short interruptions and voltage changes in the immunity test GB/T 17626.11-2008:current and voltage test error qualified
Oscillation wave immunity test GB/T 17626.12-1998:Class B ITE test, qualified

 

Product Chart